Punjab Tightens Fire Safety Rules for Multi Storey Buildings Across Province
پنجاب میں کثیر منزلہ عمارتوں کیلئے فائر سیفٹی سے تحفظ کے قوانین مزید سخت
▫️Amended regulations impose stricter requirements for emergency exits, refuge areas, fire water storage, hydrants, alarms and evacuation systems following province wide safety audit
Lahore | ReNews PakistanThe Punjab government has notified stricter fire safety regulations for multi storey residential and commercial buildings across the province, introducing enhanced requirements for emergency exits, refuge areas, f...
The Punjab government has notified stricter fire safety regulations for multi storey residential and commercial buildings across the province, introducing enhanced requirements for emergency exits, refuge areas, firefighting water reserves, hydrants, detection systems and evacuation arrangements.
The amended Punjab Community Safety Buildings Regulations 2022, updated through 2026, follow a province wide fire-safety audit and are expected to significantly affect the design, approval and operation of apartment buildings, commercial plazas, hospitals, warehouses and mixed use developments.
Under the revised regulations, every multi storey building must have at least one designated exit staircase. An additional staircase will be required for every 6,000 square feet of floor area or where occupancy exceeds 50 people on a single storey.
The maximum distance from any room to an emergency staircase has been limited to 100 feet.
Internal emergency staircases will be required to have fire rated walls, proper ventilation and outward opening fire resistant doors. Emergency lighting systems must remain operational for at least 90 minutes during a power failure, while illuminated exit signs will be mandatory along corridors and designated evacuation routes.
Buildings exceeding 100 feet in height will also be required to provide dedicated refuge areas. These spaces must remain open to the air along the building perimeter or be constructed on approved cantilever projections to provide occupants with a temporary safe area during emergencies.
Emergency staircases must remain free of obstructions and lead directly to locations accessible from adjoining roads to facilitate evacuation and rescue operations.
The amended regulations also introduce stricter requirements for firefighting infrastructure. External pillar type fire hydrants will be mandatory near building entrances and exits, while standpipe systems will be required on every floor.
These firefighting systems must operate independently of the building's normal water supply and maintain sufficient pressure through dedicated pumps with backup capacity.
Water storage requirements have also been increased.
Buildings up to 100 feet high will be required to maintain an independent 7,500 gallon overhead fire water tank. Buildings exceeding 100 feet will require a 15,000 gallon overhead tank along with a separate 30,000 gallon underground reservoir to ensure an adequate firefighting supply during disruptions to municipal water services.
At least one multipurpose fire extinguisher will be required for every 2,000 square feet of floor area. Occupants must not have to travel more than 75 feet to reach an extinguisher, while the maximum permitted distance around hazardous areas will be reduced to 30 feet.
The regulations further require video based fire and smoke detection and alarm systems in common areas and corridors, supported by uninterrupted electricity and round the clock monitoring.
Manual fire alarm call points must be installed near exits, while residential areas will need battery operated smoke detectors or automatic fire-alarm systems supported by an uninterrupted power supply.
The amended framework carries significant implications for property developers and building owners, as compliance with the enhanced requirements could become an important factor in future building approvals, safety inspections and occupancy permissions.
Developers and operators of existing multi storey buildings may therefore need to review their current designs, water storage systems, evacuation arrangements and fire safety infrastructure to ensure compliance with the updated provincial standards.